- STATE INFORMATION
- [ 2007 California Building Code‚ Title 24‚ Part 2 (First Printing)‚ includes Supplements through Jan 09 ]
- Chapter 21 - Masonry
- SECTION 2101 GENERAL
- SECTION 2102 DEFINITIONS AND NOTATIONS
- SECTION 2103 MASONRY CONSTRUCTION MATERIALS
- SECTION 2104 CONSTRUCTION
- SECTION 2105 QUALITY ASSURANCE
- SECTION 2106 SEISMIC DESIGN
- SECTION 2107 ALLOWABLE STRESS DESIGN
- SECTION 2108 STRENGTH DESIGN OF MASONRY
- SECTION 2109 EMPIRICAL DESIGN OF MASONRY
- SECTION 2110 GLASS UNIT MASONRY
- SECTION 2111 MASONRY FIREPLACES
- SECTION 2112 MASONRY HEATERS
- SECTION 2113 MASONRY CHIMNEYS
- Chapter 21 - Masonry
- [ 2007 California Building Code‚ Title 24‚ Part 2 (First Printing)‚ includes Supplements through Jan 09 ]
2113.1 Definition.
2113.2 Footings and foundations.
2113.3 Seismic reinforcing.
2113.4 Seismic anchorage.
2113.5 Corbeling.
2113.6 Changes in dimension.
2113.7 Offsets.
2113.8 Additional load.
2113.9 Termination.
2113.10 Wall thickness.
2113.11 Flue lining (material).
2113.12 Clay flue lining (installation).
2113.13 Additional requirements.
2113.14 Multiple flues.
2113.15 Flue area (appliance).
2113.16 Flue area (masonry fireplace).
2113.17 Inlet.
2113.18 Masonry chimney cleanout openings.
2113.19 Chimney clearances.
2113.20 Chimney fireblocking.
2113.19 Chimney clearances.
Any portion of a masonry chimney located in the interior of the building or within the exterior wall of the building shall have a minimum airspace clearance to combustibles of 2 inches (51 mm). Chimneys located entirely outside the exterior walls of the building, including chimneys that pass through the soffit or cornice, shall have a minimum airspace clearance of 1 inch (25 mm). The airspace shall not be filled, except to provide fireblocking in accordance with Section 2113.20.
Exceptions:
Any portion of a masonry chimney located in the interior of the building or within the exterior wall of the building shall have a minimum airspace clearance to combustibles of 2 inches (51 mm). Chimneys located entirely outside the exterior walls of the building, including chimneys that pass through the soffit or cornice, shall have a minimum airspace clearance of 1 inch (25 mm). The airspace shall not be filled, except to provide fireblocking in accordance with Section 2113.20.
Exceptions:
- 1. Masonry chimneys equipped with a chimney lining system listed and labeled for use in chimneys in contact with combustibles in accordance with UL 1777, and installed in accordance with the manufacturer's instructions, are permitted to have combustible material in contact with their exterior surfaces.
- 2. Where masonry chimneys are constructed as part of masonry or concrete walls, combustible materials shall not be in contact with the masonry or concrete wall less than 12 inches (305 mm) from the inside surface of the nearest flue lining.
- 3. Exposed combustible trim and the edges of sheathing materials, such as wood siding, are permitted to abut the masonry chimney sidewalls, in accordance with Figure 2113.19, provided such combustible trim or sheathing is a minimum of 12 inches (305 mm) from the inside surface of the nearest flue lining. Combustible material and trim shall not overlap the corners of the chimney by more than 1 inch (25 mm).
FIGURE 2113.19 ILLUSTRATION OF EXCEPTION THREE CHIMNEY CLEARANCE PROVISION
For SI: 1 inch = 25.4 mm.

